METHOD STATEMENT FOR INSTALLATION OF UNINTERRUPTIBLE POWER SUPPLY

METHOD STATEMENT FOR INSTALLATION OF UNINTERRUPTIBLE POWER SUPPLY

This document “Method Statement-Installation of Uninterruptible Power Supply” is uploaded by qhse documents in editable and ready-to-use Word format. To download more health and safety documents such as method statements, risk assessments, safety checklists, forms, JSAs, and other relatives, keep visiting on qhse documents site regularly. 

Purpose

The purpose of this Method Statement is to describe the details used and controls to be carried out for the installation of an Uninterruptible Power Supply to ensure that it complies with Project requirements, specifications, and standards.

Scope of Work

This Method Statement applies to all installations of Uninterruptible Power Supply at (project name). The workforce, machinery, devices, and equipment shall be organized to fulfill the schedule as per the approved construction project program and plan. 

Definition

Abbreviation

UPS Uninterruptible Power Supply

QAQC Quality Assurance Quality Control

MS         Method Statement 

MEP Mechanical, Electrical, Plumbing

RFIA Request for Inspection & Approval

MIR         Materials Inspection Request

ITP         Inspection and Test Plan

TBT         Tool Box Talk

 “Approved” or “Approval” 

“Approved” or “Approvals” means approved in writing by the applicable engineer's Assistant acting within the scope of their delegate authority.

“Shop Drawings” 

“Shop Drawings” means drawings produced where the contract designs drawings require expression in a more basic form to facilitate construction.

 “Final Inspection”

“Final Inspection” term means the careful and close inspection of the records of works at the accomplishment, completion, or after pre-described and pre-sit elements to make sure that all previous inspections and tests have been suitably and satisfactorily conducted and appropriately documented.

“Materials”

“Materials” means all items having the details of materials, machinery, devices, or equipment delivered to the worksite that must be integrated into the project.

“Method Statements”

“Method Statements” means a technical document to be read in conjunction with the drawings, specifications, standards, and codes of practice, technical datasheets, schedules, work instructions, and any other technical document related to a particular work.

Reference Documents – Specifications, Drawings. Etc.

  1. Project Quality Plan 
  2. Project General Specifications
  3. Approved Project Electrical Drawings
  4. Approved Method Statements
  5. Approved Material Submittal 
  6. Manufacturer’s Recommendations / Installation Instructions

Tools and Equipment  

  1. Equipment / Instrument
  2. Insulation Resistance Tester - 1000V DC
  3. Multimeter Tester

Tools

  1. Electrician Hand Tool
  2. Crimping Tools.
  3. Drilling & Grinding Machines
  4. Spanners
  5. Half-Round file
  6. Screw Drivers
  7. Open and Box Wrench
  8. Pliers
  9. Crowbar & Hammer

Manpower

Staff:

  1. Construction Manager
  2. Site Engineer
  3. Supervisor
  4. QC Engineer / Inspector
  5. Quantity Surveyor
  6. Safety Officer
  7. Labour
  8. Foreman
  9. Trade workers
  10. Helpers / Labours
  11. Drivers

Responsible Personnel on the Site

  1. The Project Manager shall be accountable for the overall construction site activities.
  2. The Construction Manager (CM), Site Engineers (SE), and Foremen shall comply with and implement this Method Statement/methodology.
  3. The Material controller shall be responsible for receiving materials on-site warehouse.
  4. The worksite engineer /supervisor shall verify and check the delivered materials as per the manufacturer's recommendation and guidelines before installation and shall be accountable for the installation as per approved and recommended shop drawings.
  5. The health and Safety Officer shall make sure that mandatory initiatives are taken at the work location/worksite to negate any unwanted events.
  6. Quality Control/Quality Assurance (QAQC) Inspector shall be accountable for conducted inspections for the materials, and substances delivered on-worksite. He shall record such inspections for legal purposes.
  7. QAQC Engineer / Inspector shall monitor the installation activities progressively and shall record all deviations from the specification in a form of snags or further non-conformance notifications.

Material Inspection / Storage

  1. Unload the UPS in the designated unloading area. Use a forklift or crane to unload UPS.
  2. Proper care must be observed during offloading to prevent unnecessary damage to UPS.
  3. Ensure that UPS is stored in a dry and clean area.
  4. Before acceptance, an inspection regarding the physical condition of the UPS shall be conducted to ensure that the components are following the Approved material submittal.
  5. Ensure that the UPS is properly protected.
  6. Submit Material Inspection Requests to the consultant for their inspection and approval.

Construction Sequence and Methodology

Preparation before Installation

  1. Ensure that Drawings for Installation are approved & coordinated with other services.
  2. The material to be used must be inspected and approved.
  3. Ensure that the material is free from damage before shifting to the areas of work. Any discrepancies, damages, etc., shall be reported for immediate further action.
  4. Before starting the work, check that proper access to execute the works is in a suitable condition and free from obstruction.
  5. Make sure that all health and safety measures and initiatives are in place.

Installation Procedure

  1. UPS systems are to be installed as per the approved drawings, as per the new approved single-line diagram for UPS attached in the material submittal.
  2. The installation will begin by placing the UPS units in the predetermined location. The input and output cables for each UPS will be connected.
  3. Battery installation will be done by placing the battery cabinet in the pre-determined location and arranging the batteries on the cabinet such that 40 batteries will fit and are accessible for maintenance.
  4. A Battery disconnection panel will also be installed near the battery racks in an accessible location as per the approved drawings. 
  5. The battery set will be connected in series using flexible double insulation single core cables (provided along with UPS).
  6. The anode and cathode of the battery set will be connected to the Battery disconnection panel. The battery disconnection panel will be connected to the UPS. Also, a control cable will be laid from the UPS to the Battery disconnection panel.
  7. All battery cabling will be done in dedicated cable trays installed on uni-strut channel supports as shown in the approved drawings.
  8. Ensure before termination of any cables that they are tested for Insulation 
  9. The UPS will be installed as per the manufacturer's recommendations

Inspection and Testing

  1. After completion of the work, the Site Engineers who perform an activity are required to raise an RFIA with complete information regarding the scope of the inspection, including the Test Report & mandatory and approved shop drawings highlighted indicating the scope of the inspection. He shall inspect their work. The inspection shall be carried out as per the typical checklist and approved Test Plans (ITP). 
  2. After Site Engineer’s completed their inspection, RFIA with the duly filled Inspection Check List shall be submitted to QAQC Department who after internal inspection shall process the documents to have the completed work inspected by Supervision Consultant for their approval.
  3. After satisfactory inspection by Supervision Consultant, completed work shall be subject to testing and commissioning.
  4. Testing and commissioning of the UPS shall be done as per manufacturer requirements. A testing report is to be submitted to the consultant for Inspection.
  5. The UPS will be tested at normal ambient conditions of the rooms where it will be installed; where it is supposed to be air-cooled, the UPS can operate at an ambient temperature of 0˚ Image 45˚C (32˚ Image104˚F) and maximum relative humidity (95%).

Note: 1. RFIA must be processed and submitted to Supervision Consultant 24 hours before the actual inspection and/or witnesses.

2. The preparatory meeting shall be carried out with the execution team as per the method statement, material submittal & shop drawings before the start of work on-site (by QA.QC Personal).

Health, Safety, and Environment

The safety of all personnel and equipment is the highest priority of the company during the execution of the Works.

Personnel Protective Equipment

  1. Safety Helmet
  2. Safety glasses/face shield (during drilling and use of grinders)
  3. Face shield (during grinding)
  4. Safety Footwear (steel toes)
  5. Safety Gloves (for material handling)
  6. Coverall (as protective clothing)
  7. Full Body Harness 
  8. Respiratory Mask (if require)

Tool Box Talk (TBT)

  1. Safety Tool Box Talk shall be given by the site supervisor every week and/or as deemed necessary.
  2. Safety tool Box Talk shall brief the task/subject and shall be given in languages understandable by the multinational workforce.
  3. The daily or weekly health and Safety Tool Box Talk attendance shall be documented on a sheet and signed by attendees.

Housekeeping

Proper and good practice of housekeeping shall be maintained by all personnel working at the worksite. Housekeeping for fabrication and installation shall be as per the project safety plan and company Safety Manual.

Signage

  1. All necessary safety warnings and caution signs shall be displayed at work locations.
  2. QC Approval and Other Documentary Requirements (Attachment)

Material Technical Submittal Approval

  1. Shop Drawing Approval
  2. Material Inspection Report (MIR) approval
  3. Installation Request for Inspection & Approval (RFIA)

DOWNLOAD FILE

Method Statement for Installation of Uninterruptible Power Supply

Post a Comment

0 Comments